The main reasons for installation of power quality meters in distribution transformer substations are power quality monitoring and global evolution of electrical network towards the smart grid. In case that all measurements from the meters are properly synchronised and centralised, new possibilities of control or evaluation of the network are enabled. This contribution proposes the possibility for an earth fault localisation with the aid of synchronised data recorded on the low-voltage side of the medium voltage/low voltage transformers in compensated neutral distribution networks which are equipped with auxiliary resistor for short-time increasing of the active part of the fault current. The described method uses voltage sags evoked by connecting of the auxiliary resistor for locating the faulty section. The proposed method is tested with the help of numerical model which presents a part of the distribution network.
Příspěvek popisuje novou metodu pro lokalizaci zemního spojení, která je založena na posouzení napěťových poklesů zaznamenaných na sekundárních stranách distribučních transformátorů VN/NN. V příspěvku je popsána metodika jak na základě zaznamenaných poklesů vymezit poruchou postiženou oblas. Metodika ja následně ověřena s využítím simulace kompenzované soustavy.
Description
Citation
IET GENER TRANSM DIS. 2015, vol. 9, issue 14, p. 2069-2077.
http://ietdl.org/t/CNR93
Document type
Peer-reviewed
Document version
Published version
Date of access to the full text
Language of document
en
Study field
Comittee
Date of acceptance
Defence
Result of defence
Document licence
Creative Commons Attribution 3.0 Unported
http://creativecommons.org/licenses/by/3.0/
Citace PRO