Temporal Development Of Relative Ablation Of Plastics In Miniature Circuit Breaker During Switching Process

Loading...
Thumbnail Image
Date
2020
ORCID
Advisor
Referee
Mark
Journal Title
Journal ISSN
Volume Title
Publisher
Vysoké učení technické v Brně, Fakulta elektrotechniky a komunikačních technologií
Abstract
The paper is focused on an ablation of plastic materials in contact with an electric arc inside the electrical apparatus during the switching process. It is possible to obtain temporal development using method based on optical emission spectroscopy. The emission spectra were taken during the switching process. The hydrogen alpha spectral line of Balmer series was used as an indicator for evaluating of plastics ablation. Complications connected with the measurements are discussed. The main part of the paper deals with a temporal development of relative concentration of a hydrogen in plasma inside the miniature circuit breaker. Atomic spectral lines database of National Institute of Standards and Technology was used as a spectral data source for evaluation.
Description
Citation
Proceedings I of the 26st Conference STUDENT EEICT 2020: General papers. s. 398-402. ISBN 978-80-214-5867-3
https://conf.feec.vutbr.cz/eeict/EEICT2020
Document type
Peer-reviewed
Document version
Published version
Date of access to the full text
Language of document
en
Study field
Comittee
Date of acceptance
Defence
Result of defence
Document licence
© Vysoké učení technické v Brně, Fakulta elektrotechniky a komunikačních technologií
DOI
Citace PRO